Plan View:Partial Perimeter Foundation System
Notes:
- NEW PRESCRIPTIVE RETROFIT METHOD
- Assumes that houses have existing perimeter foundations and cripple walls
- These standards require:
- That a completely new continuous foundation be installed along all the exterior walls, OR
- That a retrofit using a partial perimeter foundation be designed by a licensed architect or engineer and be approved by the local building official.
- Before using this method:
- The prescriptive methods and details described in this section are consistent with the Uniform Code for Building Conservation (UCBC) and City of Los Angeles standards
- Methods use partial perimeter foundation system to provide equivalent earthquake resistance below the first floor level.
- Permission to use this partial perimeter system without a specific design prepared by a licensed design professional must always be obtained from the local building official.
- PARTIAL PERIMETER VS. CONTINUOUS FOUNDATION
- Where a continuous foundation exists or is added
- Where a continuous foundation exists or is added, the primary retrofit elements used in the UCBC, are also parts of the partial perimeter system. They include:
- A foundation constructed with a concrete footing and either a poured concrete or grouted masonry stem wall.
- Foundation sill plates and sill bolts with plate washers.
- Sheathed cripple wall with connections between the wall and floor framing.
- Note that a new cripple wall is not always necessary.
- A new foundation stem wall can be extended to the underside of the existing floor framing depending on how high the existing floor is above the surrounding exterior grade.
- Generally, if the floor is more than 3 feet above grade at any point, a cripple wall will be necessary.
- Additional retrofit elements
- Several additional retrofit elements are needed for a partial perimeter system that do not occur in the UCBC prescriptive standards. They include:
- New hold-downs at the ends of new sheathed cripple walls.
- Straps to connect the existing floor framing beams and joists together and to connect them to the new partial foundations and cripple walls.
- These are load path elements needed to compensate for the use of a partial foundation system compared to a continuous foundation system
- Certain elements must be stronger or larger
- Certain elements of a partial perimeter retrofit must be stronger or larger than those prescribed in the UCBC. They include:
- Nails used to attach plywood to the cripple wall framing must be 10d common instead of 8d common.
- The minimum width of the new footing for a one-story house must be 15 inches rather than 12 inches.
- All foundation sill bolts must be 5/8-inch diameter instead of 1/2-inch, and their spacing is reduced from 6 or 4 feet on center to 2-’6” or 2’-0” on center.
(See continuation on slides 14-15)